PDF

FTG10OHM1 0,6/1 kV (PH90)

Cables for fire detection sensors, Al/Pet tape screen, fire resistant,
fire retardant, halogen free.

 

  1. Conductor
  2. Flame protection
  3. Insulation
  4. Assembling
  5. Drain wire
  6. Screen
  7. Sheath

 

APPLICATION: Suitable for the connection between the sensors and the control unit of the fire detection systems when it is required special characteristics such as: fire resistance, low smoke emission, low toxic and corrosive gases emission and the absence of halogens.

 

INSTALLATION: For fixed indoor and outdoor installation. They can be installed in cable trays, pipes, conduits and similar systems. Also for indirect burial.



FEATURES DESCRIPTION STANDARDS
Conductors: annealed red copper Cl.5 CEI EN 60228 (Tab. 9)
Flame protection: mica-glass tape, thickness >0,10 mm  
Insulation: LSZH compound, G10 quality CEI EN 50363
Cores colour:   CEI UNEL 00722 - HD 308
Assembling: Pet tape  
Drain wire: annealed tinned copper  
Screen: Al/Pet tape  
Sheath: LSZH compound, M1 quality CEI EN 50363
Sheath colour: red RAL 3000  
Fire retardant:   CEI EN 60332-3-24
Flame retardant:   CEI EN 60332-1-2
Halogen free: (< 0,5 mg/g - 0,5%) CEI EN 50267-2-1/2 - IEC 60754-1/2
Low toxic gases emission: (toxicity index < 2%) CEI 20-37/4-0
Low smoke emission: (trasmittance > 60%) CEI EN 61034-2
Fire resistant: duration 90 min. at temperature of 830 °C (- 0 ÷ + 40 °C) CEI EN 50200
DC resistance: according to CEI EN 60228 (Tab. 9)
Rated voltage Uo/U: 0,6/1 kV  
Max voltage: 1,2 kV  
Testing voltage: 4 kV  
Max working temperature: 90 °C  
Short-circuit temperature: 250 °C  
Min. installation temperature: 0 °C  
Bending radius: Ø x 14  
Max standard twisting (2x cable): ≥ 10 twist/meter  
Printing: BERICA CAVI S.P.A. ITALY FIRE RESISTANT ALARM CEI 20-22 III cat. C CEI EN 50200 PH 90 CE 0,6/1 kV Type Year/Lot 00000 m  
TYPE
N° x mm2
MEDIUM Ø OUTER
mm
MEDIUM WEIGHT
kg/km
PRODUCT CODE
2x1 8,9 82 B5602100FR
3x/G1 9,4 90,2 B5603100FR
4x/G1 10,5 115 B5604100FR
5x/G1 11,8 151 B5605100FR
7x/G1 12,8 176 B5607100FR
2x1,5 9,7 100 B5602150FR
3x/G1,5 10,3 116 B5603150FR
4x/G1,5 11,5 145,3 B5604150FR
5x/G1,5 12,8 184,1 B5605150FR
7x/G1,5 13,9 227,6 B5607150FR
2x2,5 10,9 140 B5602250FR
3x/G2,5 11,5 187 B5603250FR
4x/G2,5 12,9 235 B5604250FR
5x/G2,5 14,3 285 B5605250FR
7x/G2,5 15,6 370 B5607250FR

 

Berica Cavi Spa reserves the right to edit all the information on the website without providing prior notice to customers and / or users