PDF

FG7OH2R+T+ST 0,6/1 kV

Cables for electric motors controlled by inverter, red copper braid shield, with grounding conductor and screened pair for thermal probe outside from shield, fire retardant and low halogens emission.

 

  1. Conductor
  2. Insulation
  3. Assembling
  4. Shiled
  5. Assembling
  6. Pair for thermal probe
  7. Sheath

 

APPLICATION: Suitable for the transport of energy and in particular for the power supply of electric motors controlled by inverter. The ground conductor external to the shield and the increased coverage of the shield serve to reduce the transmission of electromagnetic noise generated by the motor control.

 

INSTALLATION: For fixed indoor installation in industrial environments. They can be installed on wall and metal structures, on platforms, pipes, conduits and similar systems. Cable for direct and indirect burial.



FEATURES DESCRIPTION STANDARDS
Conductors: annealed red copper cl.5 CEI EN 60228 (Tab. 9)
Insulation: LSZH compound, G7 quality CEI EN 50363
Cores colour: black numbered 1-2-3 CEI UNEL 00722 - HD 308
Assembling: Pet tape  
Shield: braid of annealed red copper, covering >80%  

PAIR FOR THERMAL PROBE

Conductors: annealed red copper sect. 1 mm² CEI EN 60228 (Tab. 9)
Insulation: LSZH compound, G7 quality CEI EN 50363
Cores colour: black numbered 4-5 CEI UNEL 00722 - HD 308
Assembling: Pet tape  
Drain wire: annealed tinned copper, comp. 7x0,30 mm  
Screen: Al/Pet tape  
Assembling: Pet tape  
 
Sheath: PVC, TM2 quality CEI EN 50363
Sheath colour: grey RAL 7035  
Fire retardant:   CEI 20-22/II
Flame retardant:   CEI EN 60332-1-2
Low halogens emission: (< 22%) CEI EN 50267-2-1 - IEC 60754-1
Oil resistant:   CEI 20-34/0-1
DC resistance: according to CEI EN 60228 (Tab. 9)
Current capacity:   CEI UNEL 35024/1 - CEI UNEL 35026
Rated voltage Uo/U: 0,6/1 kV  
Max. voltage: 1,2 kV  
Testing voltage: 4 kV  
Max working temperature: 90 °C  
Short-circuit temperature: 250 °C  
Min. installation temperature: 0 °C  
Bending radius: Ø x 15  
Printing: BERICA CAVI S.P.A. ITALY FG7XOH2 Type T+FG7XH Type   0,6/1 kV O.R. CEI 20-22 II CE Year/Lot  

 

TYPE
N° x mm2
MEDIUM Ø OUTER
mm
MEDIUM WEIGHT
kg/km
PRODUCT CODE
3x1,5 + 1G1,5 + 2x1 11,7 219,0 B5503150
3x2,5 + 1G2,5 + 2x1 13,2 313,0 B5503250
3x4 + 1G4 + 2x1 15,2 448,0 B5503400
3x6 + 1G6 + 2x1 17,2 591,0 B5503600
3x10 + 1G10 + 2x1 20,5 873,0 B55031000
3x16 + 1G16 + 2x1 23,4 1478,0 B55031600
3x25 + 1G25 +2x1 29,4 2010,0 B55032500

 

Berica Cavi Spa reserves the right to edit all the information on the website without providing prior notice to customers and / or users