ALARM 36762 LSZH

Cables for security systems, Al/Pet tape screen, halogen free.

  1. Conductor
  2. Insulation
  3. Assembling
  4. Drain wire
  5. Screen
  6. Sheath

Cca-s1b,d0,a1

APPLICATION: Used for connections in intrusion detection systems.In the most risky environments in the event of a fire, such as health facilities, entertainment venues and entertainment in general, gyms and sports centers. Hotels, guest houses, motels, villages, tourist residences - hotels. Schools of every level, grade and type. Exhibitors and / or retailers. Companies and offices with more than 300 people present; Libraries and archives, museums, galleries, exhibitions and exhibitions. Buildings intended for civil use, with a fire height of more than 24m.(Average Risk)

INSTALLATION: For fixed indoor installation in dry or wet environments and temporarily outdoor. They can be installed in cable trays, pipes, conduits, and similar systems. They can be laid together with power cables with marking both 450/750V, and 0.6 / 1 kV,used for systems with a nominal voltage to ground (Uo) up to 400 V.Not for direct burial.



FEATURES DESCRIPTION STANDARD
Conductors: annealed red copper cl.5 CEI EN 60228 (Tab. 9)
Insulation: LSZH compound CEI EN 50363
Cores colour: alarm colours (Tab 1) - Red-Black (power supply)
Assembling: annealed red copper 7x0,20
Drain wire: annealed red copper
Screen: Al/Pet tape
Sheath: LSZH compound CEI EN 50363
Sheath colour: white RAL 9010
Halogens free: (< 0,5 mg/g - 0,5%) CEI EN 50267-2-1/2 - IEC 60754-1/2
Testing voltage: 2000 V
Max working temperature: 70 °C
Short-circuit temperature: 160 °C
Min. installation temperature: 0 °C
Bending radius: Ø x 8
REGULATION (UE) 305/2011
System AVCP: 1+ EN 50575:2014 + A1:2016
Classification: Cca-s1b,d0,a1 UNI EN 13501-6
Cca: Heat release and flame spread(FS ≤ 2m) EN 50399
s1b: Smoke transmittance ≥ 60% <80% (TSP ≤ 50 m2 and SPR ≤ 0.25 m2 / s) EN 50399 + EN 61034-2
d0: No flaming droplets EN 50399
a1: Gas acidity (Conductivity <2.5 ms / mm and pH> 4.3) EN 50267-2-3
Flame propagation (H ≤ 425 mm) EN 60332-1-2
Printing: BERICA CAVI S.P.A. ITALY ALARM CABLE CEI UNEL 36762 C-4 (Uo = 400V) Cca-s1b,d0,a1 Type SCREENED LSZH CE, Year/ Lot

TYPE
N° x mm2
MEDIUM Ø OUTER
mm
MEDIUM WEIGHT
kg/km
PRODUCT CODE
4x0,22 5,30 23 B30C04022LSZH
6x0,22 5,60 30 B30C06022LSZH
8x0,22 5,95 36 B30C08022LSZH
12x0,226,6049B30C12022LSZH
2x0,50+2x0,226,0032B31C02022LSZH
2x0,50+4x0,226,2037B31C04022LSZH
2x0,50+6x0,226,5043B31C06022LSZH
2x0,50+8x0,226,7049B31C08022LSZH
2x0,50+10x0,227,2058B31C10022LSZH
2x0,75+2x0,226,4038B32C02022LSZH
2x0,75+4x0,226,6044B32C04022LSZH
2x0,75+6x0,226,8051B32C06022LSZH
2x0,75+8x0,227,0055B32C08022LSZH
2x0,75+10x0,227,2066B32C10022LSZH

Berica Cavi Spa reserves the right to edit all the information on the website without providing prior notice to customers and / or users