| Cores colour code: | UNEL 00722 (Tab. 8) rule | |
| Conductors: | fine stranded of bare copper | CEI EN 60228 Cl.5 (Tab. 9) |
| Flame protection: | glass fiber tape 830 °C (-0÷+40 °C) | |
| Insulation: | G10 quality thermoplastic rubber | CEI 20-11 - CEI EN 50363 rules |
| Assembling: | polyester tape: | |
| Drain wire: | fine stranded wires of tnned copper 7x0,30 mm | |
| Shield: | by aluminium/polyester tape helically wound | |
| Outer sheath: | M1 quality polymer compound | CEI 20-11 - CEI EN 50363 rules |
| Sheath colour code: | Red RAL 3000 | |
| Vertical flame retardant test: | CEI EN 60332-1-2 rule | |
| GAS emission test: | during combustion | CEI EN 50267-2-1 rule |
| Flame retardant test: | CEI EN 50266-2-4 rule | |
| Smoke's density: | during cable combustion | CEI EN 61034-2 rule |
| Toxicity of gases: | CEI 20-37/7 CEI 20-37/4-0 rules | |
| Electric resistance: | according to | CEI EN 60228 (Tab. 9) rule |
| Fire resistant test | duration 90 min. to the temperature of 830 °C (-0÷+40 °C) | CEI EN 50200 (ex CEI 20-36) rule |
| Insulation constant: | > 100 MΩ x km | |
| Working voltage: | 0,6/1 kV | |
| Testing voltage: | 4000 Vc.a. conductors/conductors x 5' - 4000 Vc.a. conductors/conductors x 5' | |
| Working temeprature: | (- 40 °C ÷ + 90 °C) | |
| Short circuit temeprature: | 250 °C | |
| Outer printing: | BERICA CAVI S.P.A. (VI) FIRE RESISTANT ALARM CEI 20-22 III cat. C CEI 20-45 PH 90 P.Q.A. CE 0,6/1 kV Nr. cond by cross section Year/Lot | |
| Bending radius: | cable outer diameter x 10 |
| TYPE | MEDIUM Ø OUTER | MEDIUM WEIGHT | ITEM CODE |
|---|---|---|---|
| nr. x mm² | mm | kg x km |
| 2x1 | 7,9 | 65,6 | B5602100FR |
| 2x1,5 | 8,9 | 85,4 | B5602150FR |
| 2x2,5 | 9,4 | 112,0 | B5603150FR |
---------
Web Design by EDIGRAF srl