SPECIAL ELECTRIC CABLES

FIRE DETECTOR CABLES FTG10OHM1 0,6/1 kV FIRE RESISTANT HALOGEN FREE

Technical Features

Cores colour code:   UNEL 00722 (Tab. 8) rule
Conductors: fine stranded of bare copper CEI EN 60228 Cl.5 (Tab. 9)
Flame protection: glass fiber tape 830 °C (-0÷+40 °C)  
Insulation: G10 quality thermoplastic rubber CEI 20-11 - CEI EN 50363 rules
Assembling: polyester tape:  
Drain wire: fine stranded wires of tnned copper 7x0,30 mm  
Shield: by aluminium/polyester tape helically wound  
Outer sheath: M1 quality polymer compound CEI 20-11 - CEI EN 50363 rules
Sheath colour code: Red RAL 3000  
Vertical flame retardant test:   CEI EN 60332-1-2 rule
GAS emission test: during combustion CEI EN 50267-2-1 rule
Flame retardant test:   CEI EN 50266-2-4 rule
Smoke's density: during cable combustion CEI EN 61034-2 rule
Toxicity of gases:   CEI 20-37/7 CEI 20-37/4-0 rules
Electric resistance: according to CEI EN 60228 (Tab. 9) rule
Fire resistant test duration 90 min. to the temperature of 830 °C (-0÷+40 °C) CEI EN 50200 (ex CEI 20-36) rule
Insulation constant: > 100 MΩ x km  
Working voltage: 0,6/1 kV  
Testing voltage: 4000 Vc.a. conductors/conductors x 5' - 4000 Vc.a. conductors/conductors x 5'  
Working temeprature: (- 40 °C ÷ + 90 °C)  
Short circuit temeprature: 250 °C  
Outer printing: BERICA CAVI S.P.A. (VI) FIRE RESISTANT ALARM CEI 20-22 III cat. C CEI 20-45 PH 90 P.Q.A. CE 0,6/1 kV Nr. cond by cross section Year/Lot  
Bending radius: cable outer diameter x 10  

Cable type

TYPE MEDIUM Ø OUTER MEDIUM WEIGHT ITEM CODE
 nr. x mm²  mm  kg x km  
2x1 7,9 65,6 B5602100FR
       
2x1,5 8,9 85,4 B5602150FR
       
2x2,5 9,4 112,0 B5603150FR

---------