SPECIAL ELECTRIC CABLES

FG7OHH2R 0,6/1 kV ALUMINIUM AND COPPER BRAID SCREENED CABLES WITH REDUCED HALOGEN EMISSION

Technical Features

Cores colour code: 3x brown, black, grey UNEL 00722 (Tab. 8) rule
Conductors: fine wires stranded of bare copper CEI EN 60228 Cl.5 (Tab. 9) rule
Insulation: G7 quality rubber CEI 20-11 - CEI EN 50363 rules
Inner sheath: thermoplastic  
1st shield:    
2nd shield braid of bare copper wires having the same cross section of the conductors (≤16 sqmm) or half of the conductors, minimum 16 sqmm (≥25 sqmm)  
Outer sheath: Rz quality PVC CEI 20-11 - CEI EN 50363 rules
Sheath colour code: Grey RAL 7035  
Vertical fire resistant test: on single conductor or insulated cable CEI EN 60332-1-2 rule
Emission gas test: during the combustion CEI EN 50267-2-1 rule
Flame retardant test:   CEI 20-22/2 rule
Electric resistance: according to CEI EN 60228 (Tab. 9) rule
Insulation constant: > 5000 MΩ x km a 20 °C  
Working voltage: 0,6/1 kV  
Testing voltage: 4 kV  
Working temperature: (- 25 °C ÷ + 90 °C)  
Short circuit temperature: 250 °C  
Outer printing: BERICA CAVI S.P.A. (VI) FG7OHH2R 0,6/1 kV CEI 20-22 II CE Year/Lot - Nr. cpnd. by cross sect. - Progr. metric  
Bending radius: cable outer diameter x 15  

Cable type

TYPE MEDIUM Ø OUTER MEDIUM WEIGHT ITEM CODE
 nr. x mm²  mm  kg x km  
3x1,5 10,5 156,0 B2403150
       
3x2,5 11,7 207,0 B2403250
       
3x4 13,1 285,0 B2403400
       
3x6 14,9 382,0 B2403600
       
3x10 17,4 596,0 B24031000
       
3x16 20,6 870,0 B24031600
       
3x25 24,5 1220,0 B24032500
       
3x35 27,5 1530,0 B24033500
       
3x50 32,1 2180,0 B24035000
       
3x70 36,4 2810,0 B24037000
       
3x95 41,5 3680,0 B24039500
       
3x120 45,4 4750,0 B240312000
       
3x150 50,4 5870,0 B240315000
       
3x185 56,4 7190,0 B240318500
       
3x240 61,9 9280,0 B240324000

---------

Web Design by EDIGRAF srl