SPECIAL ELECTRIC CABLES

FG7OH2R+T 0,6/1 kV WITH REDUCED HALOGEN EMISSION

Technical Features

Cores colour code:   UNEL 00722/VDE 0293 (Tab. 8) rule
Conductors: fine wire stranded of bare copper CEI EN 60228 Cl.5 (Tab. 9) rule
Insulation: G7 quality rubber CEI 20-11 - CEI EN 50363 rules
Assembling: polyester-mylar tape  
Shield: bare copper braid 80% covering  
Outer sheath: TM2 quality PVC CEI 20-11 - CEI EN 50363 rules
Sheath colour code: Grey RAL 7035  
Vertical fire retardant test: on single conductor or insulated cable CEI EN 60332-1-2 rule
Emission gas test: during combustion CEI EN 50267-2-1 rule
Flame retardant test   CEI 20-22/2 rule
Oil resistant test:   CEI 20-34/0-1 rule
Electric resistance: acoording to CEI EN 60228 (Tab. 9) rule
Working voltage: 0,6/1 kV  
Testing voltage: 4 kV  
Working temperature: (- 25 °C ÷ + 90 °C)  
Short circuit teperature: 250 °C  
Outer printing: BERICA CAVI S.P.A. (VI) FG7OH2R + T 0,6/1 kV O.R. CEI 20-22 II CE Year/Lot - Nr. cond. by cross sect.+ T  
Bending radius: cable outer diameter x 15  

Cable type

TYPE MEDIUM Ø OUTER MEDIUM WEIGHT ITEM CODE
 nr. x mm²  mm  kg x km  
3x1,5 + 1G1,5 10,8 173,0 B5803150
       
3x2,5 + 1G2,5 12,6 254,0 B5803250
       
3x4 + 1G4 15,3 365,0 B5803400
       
3x6 + 1G6 17,4 497,0 B5803600
       
3x10 + 1G10 20,6 730,0 B58031000
       
3x16 + 1G16 24,8 1095,0 B58031600
       
3x25 + 1G25 30,1 1680,0 B58032500

---------