| Cores colour code: | UNEL 00722 (Tab 8) | |
| Conductors: | fine wires stranded of bare copper | CEI 20-29 Cl. 5 rule |
| Insulation: | cross-linked polyethylene | CEI 20-11 rule |
| Assembling: | with protection earth cores in the interstices | |
| 1st shield: | alluminium tape with external metallic side | |
| 2nd shield: | braid of tinned copper wires | |
| Outer sheath: | TM2 quality PVC | CEI 20-11 rule |
| Sheath colour code: | transparent or black RAL 9005 | |
| Electric resistance: | according to | CEI EN 20-29 Cl. 5 (Tab 9) rule |
| Insulation constant: | >> 10000 MΩ x km | |
| Working voltage: | 0,6/1 kV | |
| Testing voltage: | 4 kV | |
| Working temperature: | -25 °C ÷ +85 °C | |
| Outer printing: | BERICA CAVI S.P.A. (VI) EMV 2XSLCY-J - Year/Lot - Nr. of cond. by cross section - Prog.Metric | |
| Bending radius: | cable outer diameter x 15 |
| TYPE | MEDIUM Ø OUTER | MEDIUM WEIGHT | ITEM CODE |
|---|---|---|---|
| nr. x mm² | mm | kg x km |
| 3x1,5+3x0,25 | 9,6 | 138 | B5703150 |
| 3x2,5+3x0,50 | 10,7 | 198 | B5703250 |
| 3x4+3x0,75 | 12,5 | 298 | B5703400 |
| 3x6+3x1 | 13,9 | 385 | B5703600 |
| 3x10+3x2,08 | 16,8 | 610 | B57031000 |
| 3x16+3x3,31 | 19,2 | 807 | B57031600 |
| 3x25+3x5,26 | 23,2 | 1130 | B57032500 |
| 3x35+3x6 | 26,2 | 1508 | B57033500 |
| 3x50+3x8,37 | 30,1 | 2250 | B57035000 |
| 3x70+3x13,3 | 35,0 | 2898 | B57037000 |
| 3x95+3x16 | 39,7 | 4084 | B57039500 |
| 3x120+3x21,15 | 45,5 | 5103 | B570312000 |
| 3x150+3x25 | 49,7 | 5895 | B570315000 |
| 3x185+3x35 | 56,4 | 7953 | B570318500 |
| 3x240+3x42,5 | 57,8 | 9496 | B570324000 |
---------